Overall performance | |
Meet standards | EMC2004/108/EC directive RoHs directive 2011/65/EU |
Working temperature | 0+50°C |
Storage temperature | -20-+70°C max. |
Working humidity | 0-95% (no condensation) |
Working environment | Public places, commercial buildings, residential buildings and other intelligent buildings, avoiding SO2 and corrosive gas environment |
Warm up time | 1 Minutes. (≤15 minutes at full specification) |
Expected service life | 15 years (ABC function enabled or regular maintenance) |
Maintenance interval | maintenance free |
Self-calibration function is on (default) | |
Power Supply | |
power supply | 24VAC/DC±20%,50/60Hz (half-wave rectifier input) |
Peak power consumption | 3VA for 24VAC 3W for 24VAC |
CO2 measurement | |
Measurement method | NDIR measurement and patented EQC coating technology with automatic calibration |
Measurement frequency | Standard 0.5Hz |
Repeat rate | ±20ppm Reading ±1% |
Accuracy 1 | ±40ppm Reading ±3% |
Pressure error | 1.6% of reading per kPa at normal atmospheric pressure |
Measuring range | 0-2000ppm |
Signal output | |
OUT1 linear conversion range | 0-5VDC 0-2000ppm 0-10VDC 0-2000ppm |
OUT2 linear conversion range | 4-20mA 0-2000pm |
Resolution | Output 1: less than 10mV |
Output 2: less than 0.02mA | |
Analog output resistance | 100Ohm max (DC) |