2. A removable six (6) pin screw terminal connector (J1) for analog output or RS-485 Digital Communication applications.
The removable connectors provide quicker installation and allows the Detector enclosure to be installed prior to the Detector Module (puck).
User Field Selectable Configuration Switches
1. The eight (8) pin DIP switch (SW2) is used to select the Detector's Sensitivity and Relay Options.
2. The ten (10) pin DIP switch (SW1) is used for:
• Selecting a unique digital address (128 choices).
• Factory Use
3. The ten (10) position Rotary switch allows selection of the analog and digital communication protocol.
1.2 Detector Technical Specifications
1.2.1 Mechanical Specifications Enclosure Material: Copper Free Aluminum
316 Stainless Steel
Physical Dimensions: Assembly 4.35 in. (110.49 mm) Height X 4.81 in. (122.24 mm) Diameter
Mounting Holes ¼ in. (6.35 mm) Diameter, 5.50 in. (139.70 mm) Center to Center
Conduit Entries Two (2) ¾ in. NPT or Two (2) 25 mm
Weight: Aluminum 3 lbs. 11 oz. (1.7 kg) approximately
Stainless Steel 7 lbs. 7 oz. (3.4 kg) approximately
Enclosure Rating: IP66 / NEMA 4X
Vibration: Meets or exceeds Mil Spec 810C,
Method 514.2, Curve AW
1.2.2 Electrical Specifications
Input Voltage Range: 18 VDC to 32 VDC
Normal Operation Current: 60 mA (nominal) 205 mA (nominal with heater1)
Maximum Fire Alarm Current: 85 mA (maximum) 235 mA (maximum with heater1)
Relay Contact Rating: 1 Amp @ 24 VDC resistive
Analog Current Output: 0 to 20 mA (Source or Sink, User Selectable)
(400 Ohms Max Load) 0.0 mA (<0.6 mA) =Fault
2.0 mA (±0.6 mA) = Dirty Window Lens
4.0 mA (±0.6 mA) = Normal, Safe (no Fault, no Fire)
20.0 mA (±0.6 mA) = Alarm or Verified Fire Alarm
Screw Terminal Wire Sizes: 12 AWG to 22 AWG (2.50 mm to 0.762 mm)
Use stranded conductors (not solid core)
1.2.3 Environmental Specifications
Operating Temperature, Standard: -40° F to +185° F (-40° C to +85° C) for FS24X-2 (110° FoV)
Operating Temperature, Standard: -76° F to +185° F (-60° C to +85° C) for FS24X-9 (90° FoV)
Operating Humidity Range: 0 to 95% RH,
100% RH condensing for short periods of time
Storage Temperature: -67° F to +221° F (-55° C to +105° C)
1.2.4 Performance Specifications2
Field of View: FS24X detectors have a cone of view of 90° horizontal and
80° vertical with the highest sensitivity on the central axis
Sensitivity: One (1) sq. ft. heptane reference fire at 200 feet
Speed of Response: 2 to 5 seconds (typical)
Spectral Sensitivity: 0.4 microns to 5.0 microns