General | |||||||||||||
Rated power supply voltage | 100 to 240V AC 50/60Hz, 8VA max. 15 to 50V DC, 10VA max. |
||||||||||||
Insulation Resistance | Over 10MΩ under DC500V megger between input terminal and case(ground). Over 10MΩ under DC500V megger between output terminal and case(ground). |
||||||||||||
Withstand voltage | 1000V AC 50/60Hz for 1min across input terminal and case(ground) 1500V AC 50/60Hz for 1min across output terminal and case(ground) |
||||||||||||
Standard Conditions |
Ambient Temp. | 23 ± 2 .C | |||||||||||
Ambient Humi. | 60 ± 5% RH | ||||||||||||
Rated Power Supply | 110V AC | ||||||||||||
Power Frequency | 50 ± 1Hz or 60 ± 1HZ | ||||||||||||
Operating Conditions |
Ambient Temp. | 0 to 50.C | |||||||||||
Ambient Humi. | 20 to 90%RH (non-condensing) | ||||||||||||
Rated Power Supply | 100 to 240V AC 20 to 50V DC |
||||||||||||
Allowable Power Supply |
85 to 264V AC 15 to 55VDC |
||||||||||||
Power Frequency | 50 ± 2Hz or 60 ± 2Hz | ||||||||||||
Vibration Resistance | 10m/s2 (approx. 1G), 10 to 55Hz for 10min each X, Y, Z directions | ||||||||||||
Transportatio n and storage conditions |
Ambient Temp. | -20 to +65 .C | |||||||||||
Ambient Humi. | 10 to +95% RH (non-condensing) | ||||||||||||
Vibration Resistance | 20m/s2 (Approx. 2G), 10 to 55Hz for 2 hours each in X, Y, Z directions | ||||||||||||
Exterior | Case and front panel : plastic | ||||||||||||
Mounting | Panel-mount | ||||||||||||
Model | DC1010 | DC1020 | DC1030 | DC1040 | |||||||||
Exterior Size : W X H X D |
50 X 50 X 97 (1.97X1.97X 3.82) |
50 X 96 X 97 (1.97X3.78X3.82) |
74 X 74 X 97 (2.91X2.91X3.82) |
96 X 96 X 97 (3.78X3.78X3.82) |
|||||||||
Panel Cutout : W X H |
44.5 X 44.5 (1.75 X 1.75) |
44.5 X 90.5 (1.75 X 3.56) |
68.5 X 68.5 (2.97 X 2.97) |
90.5 X 90.5 (3.56 X 3.56) |
|||||||||
Global Approvals | CE, cUL | ||||||||||||
Interval = 20.5mm (0.807 in) |
Model | DC1010 | DC1020 | DC1030 | DC1040 | |||||||||
Input/Output | |||||||||||||
Analog Output 1 |
Relay | SPST | SPDT | SPST | SPDT | ||||||||
3A, 220Vac, Resistive Load(100,000 time electrical life) | |||||||||||||
Voltage Pulse | PWM(SSR drive), ON: 20 Vdc, OFF: 0 V (max. load current 20mA) Open Time Terminal Voltage: 20 Vdc or less Time Proportional Cycle Time: 0-150 sec |
||||||||||||
Linear | DC Current (mA) DC Voltage (V) Accuracy Update Cycle |
: 0~20mA, 4~20mA (load resistance 500Ω) : 0~5V, 0~10V, 1~5V, 2~10V (max. load current 20mA) ± 5% of Span 500m sec |
|||||||||||
Analog Output 2 (* Note 1) |
Relay | SPST | SPST | SPST | SPST | ||||||||
3A, 220Vac, Resistive Load(100,000 time electrical life) | |||||||||||||
Voltage pulse | PWM(SSR drive), ON: 20 Vdc, OFF: 0 V (max. load current 20mA) Open Time Terminal Voltage: 20 Vdc or less Time Proportional Cycle Time: 0-150 sec |
||||||||||||
Linear | DC Current (mA) DC Voltage (V) Accuracy Update Cycle |
: 0~20mA, 4~20mA (load resistance 500Ω) : 0~5V, 0~10V, 1~5V, 2~10V (max. load current 20mA) ± 5% of Span 500m sec |
|||||||||||
Output Direction (OUD) | HEAT(Direct)/COOL(Reverse) (Selectable) | ||||||||||||
Control Mode | Auto/Manual operation is switchable. *Manual output : Bumpless in normal mode OUTL in abnormal mode |
||||||||||||
Transmission Output |
Object | SP, PV | |||||||||||
No. of point | 1 point | ||||||||||||
Type | 4-20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V | ||||||||||||
Accuracy | +/- 0.2% of span | ||||||||||||
Update Cycle | 500 ms | ||||||||||||
Digital Output | Relay | AL1 | SPST | SPDT | SPST | SPDT | |||||||
AL2 | SPST | SPDT | SPST | SPDT | |||||||||
AL3 | - | SPST | SPST | SPST | |||||||||
3A, 220Vac, Resistive Load(100,000 time electrical life) | |||||||||||||
* For Heat/Cool Control Output only. |
PID Control & Auto-Tuning | |||||||||||||
Proportional Band (P1,P2) | Proportional Band: 0.0 ~ 200.0% | ||||||||||||
Integral time (I1, I2) | Integral time : 0 ~ 3600 sec | ||||||||||||
Derivative time (D1, D2) | 0 ~ 900 sec | ||||||||||||
Auto-Tuning Value | 0 ~ USPL | ||||||||||||
HYS1, HYS2 | 0 ~ 1000 (for ON/OFF control) | ||||||||||||
Dead Band (DB1) | Not defined. | ||||||||||||
GAP1, GAP2 | 0 ~ 1000(for HEAT/COOL control) | ||||||||||||
Cycle Time | 0 ~ 150 sec | ||||||||||||
Communication | |||||||||||||
Speed | 1200, 2400, 4800, 9600, 19200, 38400 bps | ||||||||||||
Protocol | ModBus RTU, ModBus ASCII | ||||||||||||
Parity check | Odd / Even | ||||||||||||
Bit length | 8 | ||||||||||||
Communication | RS232C, RS485 | ||||||||||||
Events(ALARMS) | |||||||||||||
PV Event | Code | 01 / 11 | Deviation-High alarm (inhibit / no-inhibit) | ||||||||||
02 / 12 | Deviation-Low alarm (inhibit / no-inhibit) | ||||||||||||
03 / 13 | Deviation High/Low Limit alarm (inhibit / no-inhibit) | ||||||||||||
04 / 14 | Deviation High/Low Limit range alarm (inhibit / no-inhibit) | ||||||||||||
05 / 15 | Absolute High alarm by PV (inhibit / no-inhibit) | ||||||||||||
06 / 16 | Absolute Low alarm by PV (inhibit / no-inhibit) | ||||||||||||
SET VALUE | -1999~ USPL (Absolute value, Deviation value) | ||||||||||||
Activation Hysterisis | 0 ~ 1000 | ||||||||||||
On Delay Time | 0 : Flicker 99M 59S : Continuance 00M 01S to 99M 58S : Time Delay |
||||||||||||
Program | Code | 07 | Segment End alarm(in progress of program) | ||||||||||
17 | Program RUN | ||||||||||||
System | Code | 08 | System Error ON | ||||||||||
18 | System Error OFF | ||||||||||||
TIME | Code | 19 | Delaying timer (00Hours 00Min ~ 99Hour 59Min) | ||||||||||
HBA | Code | 09 | Heater Break Alarm |
Program (Optional) | |||||||||||||
Program section | No. of programs | 2 (Program 1 & Program 2) | |||||||||||
No. of segments | 8 segments/1 program | ||||||||||||
Segment time | Segment time: Setting by set points(SP) and time (Max. 99hours 59minutes) |
||||||||||||
Control output | 0~100% When OUT=0%, Program End. |
||||||||||||
WAIT function | Rear Wait Time may exceed set time of the particular segment. In this case, remaining time is set as 0 and pending; if the temperature that was measured does not reach target value ± WAIT set point. It proceeds to the next segment after it is confirmed that temperature reach the range of set point (target value ± WAIT) |
||||||||||||
Setup range: ± 0 ~ 1000 by decimal point. | |||||||||||||
Repeat | Repeat / Non-repeat | ||||||||||||
Program link | When Program number is 0, Link program 1 and 2. | ||||||||||||
Program start | (1) Start from SP=0 (2) Start from PV |
||||||||||||
Power Failure | Hot Start / Cold Start | ||||||||||||
TIME UNIT | Hour. Minute / Minute. Second | ||||||||||||
Ramp & Soak | |||||||||||||
Slope(Ramp) | Temperature : 0.0 to 99.99 / min | ||||||||||||
SOAK TIMER | Max. 99 hours 59 min | ||||||||||||
POWER FAILURE | It starts from PV. |
Analog Input Range (Thermocouple) | |||||||||||||
Input Type | Code | Temperature Range | Indication Accuracy |
Remarks | |||||||||
ºC | ºF | ||||||||||||
TC (Note1) |
K | K1 | 0.0~200.0 | 0.0~392.0 | +/-0.2%FS | ||||||||
K2 | 0.0 ~ 400.0 | 0.0~752.0 | |||||||||||
K3 | 0 ~ 600 | 0~1112 | |||||||||||
K4 | 0 ~ 800 | 0~1472 | |||||||||||
K5 | 0 ~ 1000 | 0~1832 | |||||||||||
K6 | 0 ~ 1200 | 0 ~ 2192 | |||||||||||
J | J1 | 0.0~200.0 | 0.0~392.0 | +/-0.2%FS | |||||||||
J2 | 0.0 ~ 400.0 | 0.0~752.0 | |||||||||||
J3 | 0 ~ 600 | 0~1112 | |||||||||||
J4 | 0 ~ 800 | 0~1472 | |||||||||||
J5 | 0 ~ 1000 | 0~1832 | |||||||||||
J6 | 0 ~ 1200 | 0 ~ 2192 | |||||||||||
R | R1 | 0~1600 | 0~2912 | +/-0.2%FS | +/-2 ºC under 100 ºC +/-3.6 ºF under 212 ºF |
||||||||
R2 | 0~1769 | 0~3216 | |||||||||||
S | S1 | 0~1600 | 0~2912 | +/-0.2%FS | |||||||||
S2 | 0~1769 | 0~3216 | |||||||||||
B1 | 0~1820 | 0~3308 | +/-0.2%FS | No guarantee at 0 ~ 400ºC | |||||||||
E | E1 | 0~800 | 0~1472 | +/-0.2%FS | |||||||||
E2 | 0~900 | 0~1652 | |||||||||||
N | N1 | 0~1200 | 0~2192 | +/-0.2%FS | |||||||||
N2 | 0~1300 | 0~2372 | |||||||||||
T | T1 | -199.9~400.0 | -199.9~752.0 | +/-0.2%FS | +/-1 ºC under -100 ºC +/-1.8 ºF under -148 ºF |
||||||||
T2 | -199.9~200.0 | -199.9~392.0 | |||||||||||
T3 | 0.0~350.0 | 0.0~662.0 | +/-0.2%FS | ||||||||||
W5Re/ W26Re |
0~2300 | 0~3632 | +/-0.2%FS | ||||||||||
0~2320 | 0~4208 | ||||||||||||
PLII | PL1 | 0~1300 | 0~2372 | +/-0.2%FS | |||||||||
PL2 | 0~1390 | 0~2534 | |||||||||||
U | U1 | -199.9~600.0 | -199.9~999.9 | +/-0.2%FS | +/-1 ºC under -100 ºC +/-1.8 ºF under -148 ºF |
||||||||
U2 | -199.9~200.0 | -199.9~392.0 | |||||||||||
U3 | 0.0~400.0 | 0.0~752.0 | +/-0.2%FS | ||||||||||
L | L1 | 0~400 | 0~752 | +/-0.2%FS | |||||||||
L2 | 0~800 | 0~1472 |
Analog Input Range (RTD) | |||||||||||||
Input Type | Code | Input Type | Indication Accuracy |
Remarks | |||||||||
ºC | ºF | ||||||||||||
RTD | JPt100 | JP1 | -199.9~600.0 | -199.9~999.9 | +/-0.2%FS | +/-0.5 ºC under -100 ºC +/-0.9 ºF under -148 ºF |
|||||||
JP2 | -199.9~400.0 | -199.9~752.0 | |||||||||||
JP3 | -199.9~200.0 | -199.9~392.0 | |||||||||||
JP4 | 0~200 | 0~392 | |||||||||||
JP5 | 0~400 | 0~752 | |||||||||||
JP6 | 0~600 | 0~1112 | |||||||||||
DIN Pt100 |
DP1 | -199.9~600.0 | -199.9~999.9 | +/-0.2%FS | +/-0.5 ºC under -100 ºC +/-0.9 ºF under -148 ºF |
||||||||
DP2 | -199.9~400.0 | -199.9~752.0 | |||||||||||
DP3 | -199.9~200.0 | -199.9~392.0 | |||||||||||
DP4 | 0~200 | 0~392 | |||||||||||
DP5 | 0~400 | 0~752 | |||||||||||
DP6 | 0~600 | 0~1112 | |||||||||||
JPt50 | JP.1 | -199.9~600.0 | -199.9~999.9 | +/-0.2%FS | +/-0.5 ºC under -100 ºC +/-0.9 ºF under -148 ºF |
||||||||
JP.2 | -199.9~400.0 | -199.9~752.0 | |||||||||||
JP.3 | -199.9~200.0 | -199.9~392.0 | |||||||||||
JP.4 | 0~200 | 0~392 | |||||||||||
JP.5 | 0~400 | 0~752 | |||||||||||
JP.6 | 0~600 | 0~1112 |
Analog Input Range (Linear) | |||||||||||||
Input Type | Code | Source | Range | Indication Accuracy |
Remarks | ||||||||
Linear | AN1 | -10~10mV | -1999~9999 | +/-0.1% of span | |||||||||
AN2 | 0~10mV | ||||||||||||
AN3 | 0~20mV | ||||||||||||
AN4 | 0~50mV | 0-20mA, 0-1V, 0-5V, 0-10V | |||||||||||
AN5 | 10~50mV | 4-20mA, 1-5V, 2-10V |