Customization: | Available |
---|---|
Function: | Automatic Control, Protection, Monitoring, Measurement |
Certification: | RoHS, CCC, ISO: 9001, CE |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical data | |||||
PV Input | Type of Input | Thermocouples : K, J, R, S, B, E, N, T, W, PL II, U, L | |||
RTD : Pt100, JPt100, JPt50 | |||||
Linear : 4~20mA | |||||
Input Sampling Time | 250 ms | ||||
Input Resolution | 14 bit (each) | ||||
Indication | PV/SP Indication | 4-digit, 7 segment display | |||
Constant Value Storage System | Non-volatile memory (EEPROM) | ||||
Indication Accuracy | +/-0.2%FS | ||||
Control Mode | Proportional Band ( P ) | 0~200% (On/Off action at P=0) | |||
Integral Time ( I ) | 0~3600 sec (PD action at I=0) | ||||
Derivative Time ( D ) | 0~900 sec (PI action at D=0) | ||||
Cycle Time | 0~150 sec (4~20mA=0, SSR=1, Relay=10) | ||||
Dead Band Time | 0~1000 sec (dead time compensation) | ||||
Output | Relay Output | Electromechanical relay • SPDT contacts (DC101 :SPST) • 3A/240Vac |
|||
Static relay driver output | Voltage Pulse, 20VDC/20mA | ||||
Current & Voltage outputs | 0~20mA, 4~20mA, 0~5V, 0~10V, 1~5V, 2~10V |
||||
Motor Control Output | Servo motor valve control (open loop circuit) | ||||
Others | Phase angle control : 1ϕ SSR, 3ϕ SSR, 1ϕ SCR, 3ϕ SCR |
||||
Alarm | Number | Up to 3 (optional, DC101 :2sets) | |||
Modes | 17 alarm modes available, hability to ignore the alarm the first time it occurs : Deviation high or low alarms. Deviation alarms. Band alarm. High or low alarm. End of segment alarm. Program run indication alarm. Timer alarm. |
||||
Timer | One timer is associated with each alarm. | ||||
Retransmission output |
Output Signal | SP, PV | |||
Type of Output | 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V | ||||
2nd Input (Remote SP) |
Type of Input | 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V | |||
Sampling Time | 500 ms. | ||||
Programs | Number | 2 programs of 8 segments each. | |||
Communication |
Type of Communication | RS-232 or RS-485. Modus rtu(HEX), Modbus ASCII | |||
Specification | Partity= Odd/Even, Data bit= 8bits, Stop bit=1 or 2 bit |
||||
Communication Speed | 2400,4800,9600,19200,38400 bps | ||||
Operating conditions |
Rated Power Supply Voltage & Frequency |
AC 85 ~ 265V, 50/60Hz DC24V(optional) |
|||
Power Consumption | 8VA (110V), 12VA (220V) | ||||
Ambient Temperature | -20°C ~ 65°C (-4°F ~ 149°F) | ||||
Ambient Humidity | 50 ~ 85% RH (non condensing) | ||||
Approvals | UL (QUXY2-E201698) CE Mark. |