The ST17H intelligent temperature transmitter provides an economical solution for temperature detection applications. The ST17H is more accurate, safe and reliable, and reduces the cost of wiring compared to the directly connected temperature measuring points. The temperature signal output of this temperature transmitter is automatically linearized within the upper and lower limits set by the user. In addition,users can program high - and low-limit alarm points and make them alarm if the sensor fails.
Characteristics:
• HART/4-20mA output
• Thermal resistance,thermocouple, resistance value or millivolt input
• Single or dual sensor (difference or average) input
• Type B DIN rail or head mount
• It can be connected with HART multipoint mode
• Sensor fault signals comply with NAMUR NE43
• It is configured using the STT17C configuration tool and PC or HART field configuration
• Electrical isolation
Applications:
• Support PT100/PT1000 thermal resistance
• 8 kinds of thermocouples
Sensory type |
Basic accuracy 1 |
Rated range |
Standard |
Minimum range2 |
The temperature effect of every 1.0ºC 3 change in ambient temperature |
Fixed value |
% of the range |
ºC |
Fixed value |
% of the range |
ºC |
Pt100 |
0.15ºC |
±0.1 |
-200~+850 |
IEC60751 |
10ºC |
0.01ºC |
±0.1 |
Pt1000 |
0.2ºC |
±0.1 |
-200~+850 |
IEC60751 |
10ºC |
0.01ºC |
±0.1 |
Ni100 |
0.3ºC |
±0.1 |
-60~+250 |
DIN43760 |
10ºC |
0.01ºC |
±0.1 |
B |
1ºC |
±0.1 |
+400~+1820 |
IEC584 |
100ºC |
0.2ºC |
±0.1 |
E |
0.5ºC |
±0.1 |
-100~+1000 |
IEC584 |
50ºC |
0.05ºC |
±0.1 |
J |
0.5ºC |
±0.1 |
-100~+1200 |
IEC584 |
50ºC |
0.05ºC |
±0.1 |
K |
0.5ºC |
±0.1 |
-180~+1372 |
IEC584 |
50ºC |
0.05ºC |
±0.1 |
L |
0.5ºC |
±0.1 |
-100~+900 |
DIN43710 |
50ºC |
0.05ºC |
±0.1 |
N |
0.5ºC |
±0.1 |
-180~+1300 |
IEC584 |
50ºC |
0.05ºC |
±0.1 |
R |
1ºC |
±0.1 |
-50~+1760 |
IEC584 |
100ºC |
0.2ºC |
±0.1 |
S |
1ºC |
±0.1 |
-50~+1760 |
IEC584 |
100ºC |
0.2ºC |
±0.1 |
T |
0.5ºC |
±0.1 |
-200~+400 |
IEC584 |
50ºC |
0.05ºC |
±0.1 |
U |
0.5ºC |
±0.1 |
-200~+600 |
DIN43710 |
50ºC |
0.05ºC |
±0.1 |
W3 |
1ºC |
±0.1 |
0~+2300 |
ASTM E988-90 |
100ºC |
0.2ºC |
±0.1 |
W5 |
1ºC |
±0.1 |
0~+2300 |
ASTM E988-90 |
100ºC |
0.2ºC |
±0.1 |
Ω |
0.1Ω |
±0.1 |
0~7000Ω |
|
25Ω |
5mΩ |
±0.1 |
mV |
10μV |
±0.1 |
-800~800mV |
|
5mV |
0.5μV |
±0.1 |
- Select the larger value, the overall reference accuracy = basic accuracy
- Or 50% of the upper limit value of the range, choose the larger value
- Reference temperature 24ºC
Table 1. Performance parameters
Operating condition
Ambient temperature (rated) |
-40~85ºC |
Humidness |
0~95%RH |
Vibration |
Max. 4g(25~100Hz) |
Cold end accuracy |
±1.0ºC |
Electrical input characteristic
Power source |
9~30VDC |
Supply voltage effect |
≤0.005% range /VDC |
Preheating time |
30s |
Response time (configurable) |
1~60s |
Electrical isolation |
1500VAC |
Current output characteristic
Signal output range |
4~20mA |
Refresh time |
440ms |
Loop resistance |
≤(Power supply-7.2)/0.023A 0~870Ω |
Warning
Configurable |
3.5~4mA Upscale 20~23mA Downscale |
NAMUR NE43 Upscale |
23mA |
NAMUR NE43 Downscale |
3.5mA |
Ex certification
KEMA 06 ATEX 0042 X |
II I GD,T80ºC ⋯T105ºC EEX ia IIC T4⋯T6 |
T4 Maximum ambient temperature |
85ºC |
T6 Maximum ambient temperature |
60ºC |
Application area |
0,1,2,20,21 and 22 |
Ex data
Ui(max) |
30VDC |
Ii(max) |
120mADC |
Pi(max) |
0.84W |
Li(max) |
10μH |
Ci(max) |
1.0nF |
Uo(max) |
9.6VDC |
Io(max) |
25mADC |
Po(max) |
67mW |
Lo(max) |
33mH |
Co(max) |
3.5μF |